presentations
|
about us |
products
|
testimonials
|
specifications
|
contracting
|
contact us
|
home |
links
|
news releases
Specifications
for Gasoline Fueling System
All Gasoline Fueling Systems
Shall Consist of the Following:
I. Tank
II. Containment
Vessel
III. Receiving
System
IV. Delivery
System
V. Vapor
Recovery System
VI. Electrical
System
VII. Alarm
System
VIII. Control
Panel
IX. Piping
X. Factory
Assembled
XI. Copyright
I. Tank
A.
Shall be designed, constructed, and
labeled per UL142 specifications.
B.
Shall be of single wall
construction, with all seams and fittings welded both inside and
outside tank.
C.
Shall be horizontal and include UL
approved integrated support saddles for zone 4 seismic
conditions.
D.
Shall show date of manufacturer’s
test and manufacturer’s name.
E.
Shall be labeled for stationary use
only.
F.
Shall include lifting eyes, for use
when empty only, to lift complete unit.
G.
Shall have CAL/OSHA approved ladder
on tank.
H.
Shall have permanent gauge stick in
tank.
I.
Shall be pressure tested to 5 PSI
with all valves and fittings in place.
J.
Shall have a manway with inspection
port.
K.
Shall have a low point drain with a
locking, non-freezing valve.
L.
Shall have a normal vent as
required.
M.
Shall have an emergency vent to meet
or exceed NFPA-30 Firecode.
II. Containment
Vessel
A.
Shall be designed, constructed, and
labeled per UL142 specifications.
B.
Shall be of steel construction
minimum 10 gauge.
C.
Shall be capable of containing over
110% of the volume of the tank.
D.
Shall not exceed 12’ (twelve feet)
in width.
E.
Shall be skid-mounted, relocatable.
F.
Shall have a locking, low point
drain valve.
G.
Shall have lifting hooks on the
containment ends accessible form outside the containment wall.
H.
Shall have a leak detection alarm.
I.
Shall be leak tested with full load
of water after assembly.
III. Receiving
System
A.
Shall have a drylock fill system
that prevents spillage of product during filling process.
B.
Shall have vapor return line with
kamvalock fitting that prevents leakage of vapor during filling
process.
C.
All fill, vapor line, and fittings
used for filling the tank shall be inside the containment wall.
D.
Shall have stage 1 vapor recovery.
E.
Shall be top filled with drop tube
within 6” of tank bottom.
F.
All filling procedures done at
ground level (with operator outside of containment).
IV. Delivery
System
A.
Shall have a self-sealing emergency
valve.
B.
Shall have a 212 degree F. fusible
link that allows emergency valve to close in case of fire.
C.
Emergency valve shall be operated
outside of containment.
D.
Shall have U.L. approved 12 gpm
(twelve gallons per minute) commercial pump with the following:
1.
Shall have 1/3 H.P. motor
2.
Shall have 110 volt single-phase
electrical power requirement.
3.
Shall have remote control
capability.
4.
Shall have register with automatic
reset interlock.
5.
Shall register to 999.0 gallons per
delivery.
6.
Shall have totalizer register up to
999,999.9 gallons.
E.
Shall have a Tohkeim Model 52
pressure regulator valve.
F.
Shall have a 10 (ten) micron filter
system.
G.
Shall have a high hose retractor.
H. All delivery operations shall be
from ground level outside of containment.
V. Vapor
Recovery System
A.
Vapor recovery system shall operate
on a vacuum.
B.
Shall be California Air Resources
Board Certified, per Executive Order
#G-70-128 or #G-70-139
C.
Shall have a VCS-200 vapor
processor.
D.
Shall be capable of being
retrofitted for Stage II vapor recovery with the addition of
required piping, co-axial hose, and vapor processor.
VI. Electrical
System
A.
All electrical components shall meet
all applicable NEMA and U.L. Standards for Class 1, Group D
equipment.
B.
All wiring shall conform to all
applicable NEC standards for Class 1, Group D equipment.
C.
Area lighting shall be activated by
an on/off switch.
D.
Control circuits shall be 120 volt.
E.
Area and alarm lights shall be
explosion-proof.
F.
Power requirements are single phase;
120 vac, 20 amp at load connection.
G.
Float switch in containment shall be
intrinsically safe.
H.
All operational modes (fill or
dispense), shall be done from ground level outside of
containment.
VII. Alarm
System
A.
Shall be Class 1, Group D.
B.
Shall be both audible and visual.
1.
Audible alarm shall incorporate an
alarm silence, which will allow subsequent activation of audible
alarm.
2.
Visual alarm shall be a flashing
light that will not reset until alarm condition has been
cleared.
C.
System shall alarm at the following
conditions
1.
High and low tank level alarm –
power to pump is cut off, and restored with alarm silence.
2.
High and low cut off – power to pump
is cut off and restored with auto maintenance selector switch.
3.
Liquid in containment – power to
pump is cut off and restored with auto maintenance selector
switch
VIII. Control
Panel
A.
All
electrical components shall be controlled by a Bryant Fuel
System control panel installed inside a U.L. listed, NEMA – 4
box. This control panel is mounted on exterior containment walls
and operates in conformance with Class 1 Group D areas.
1. Control
panel shall be mounted and
wired to quick disconnect devices.
2. Control
panel shall operate from –40
degree Celsius to +180 degree Celsius.
B.
Control Panel shall have the
following:
1.
Will shut down all arching devices
on overfill or liquid in containment alarm.
2.
Emergency shut-off button.
3.
Alarm indicator lights.
4.
Alarm reset.
5.
Automatic/maintenance selector
switch (key operated).
6.
Gauge for tank level (in percent).
7.
Panel light test.
IX. Piping
A.
Shall be minimum schedule 40 with
forged steel fittings.
B.
Shall have flanged connections where
possible.
C.
Shall have pressure relief to
prevent pressure build-up from thermal expansion.
X. Factory
Assembled
A.
All assembly shall be with cadium
plated bolts, nuts, and lock washers.
B.
All units shall be commerciall y
sandblasted before painting.
C.
All paint shall be fire resistant.
D.
All units shall be completely
assembled and operationally tested with approved testing fluid
prior to delivery.
E.
Emergency generator access shall be
supplied if requested.
F.
Tank, containment, saddles, and
ladder shall be U.L. 58-02-03 listed as a unit.
G.
Entire unit assembled not to exceed
35,000 pounds empty.
H.
The complete fuel system shall be
self-contained with only the addition of electrical power
necessary to be a fully operational turnkey system.
XI. Copyright
A.
All units are copyrighted and
patented. Anyone attempting to duplicate the
construction/manufacture of the Bryant Fuel Cell without the
express written consent of Bryant Fuel Systems may be violation
of copyright or patent laws.
B.
Copyright Bryant Tank, Inc. 1994.