I. Tank
A.
Shall be designed,
constructed, and labeled per UL142 specifications.
B.
Shall be of single
wall construction, with all seams and fittings welded both
inside and outside tank.
C.
Shall be
horizontal and include UL approved integrated support
saddles for zone 4 condition.
D.
Shall show date
manufacturer’s test and manufacturer’s name.
E.
Shall be labeled
for stationary use only.
F.
Shall include
lifting eyes, for use when empty only, to lift complete
unit.
G.
Shall have CAL/OSHA
approved ladder on tank.
H.
Shall have
permanent gauge stick in tank.
I.
Shall be pressure
tested to 5 PSI with all valves and fittings in place.
J.
Shall have manway
with inspection port.
K.
Shall have a low
point drain with a locking, non-freezing valve.
L.
Shall have a
normal vent
M.
Shall have an
emergency vent to meet or exceed NFPA-30 Firecode.
II.
Containment
Vessel
A.
Shall be designed,
constructed, and labeled per UL142 specifications.
B.
Shall be of steel
construction, minimum 10 gauge.
C.
Shall be capable
of containing over 110% of the volume of the tank.
D.
Shall not exceed
12’ (twelve feet) in width.
E.
Shall be
skid-mounted, relocateable.
F.
Shall have a
locking, low point drain valve.
G.
Shall have lifting
hooks on the containment ends accessible from outside the
containment wall.
H.
Shall have a leak
detection alarm.
I.
Shall be leak
tested with full load of water after assembly.
III.
Receiving
System
A.
System shall be
able to off-load vehicles and equipment.
B.
Pump shall be
rated at not less than 50 gpm (fifty gallons per minute).
C.
Pump motor shall
be rated 220 three-phase 1 ½ H.P.
D.
All filling
procedures shall be done at ground level (with operator
outside of containment).
E.
Shall have pumping
system for unloading deliveries.
F.
Shall have a
seal-sealing emergency valve threaded directly in to the
tank, with breakaway provisions.
G.
Shall have a
212-degree F. fusible link that allows emergency valve to
close in case of fire.
H.
Shall have
dry-lock system that prevents spillage of product.
IV.
Electrical
System
A.
All electrical
components shall meet all applicable NEMA and UL Standards
for Class 1, Group D.
B.
All wiring shall
conform to all applicable NEC Standards for Class 1, Group
D.
C.
Area lighting
shall be switch activated.
D.
Control circuits
shall be 120 volts.
E.
Area and alarm
lights shall be explosion proof.
F.
Alarm horn shall
be explosion proof.
G.
Power requirements
are three phase, 220 vac, 20 amps at load connection.
H.
Float switch in
containment shall be intrinsically safe.
V.
Alarm System
A. Alarm
shall be Class 1, Group D.
B.
Alarm shall be
both audible and visual.
1. Audible
alarm shall incorporate an alarm silence which will allow
subsequent activation of audible alarm.
2.
Visual alarm
shall be a flashing light that will not reset until alarm
condition has been cleared.
C. System
shall alarm on the following conditions:
1.
High tank alarm;
audible alarm is silenced with reset button.
2.
High tank cut-off;
power to pump is cut-off and restored with auto maintenance
selector switch.
3.
Liquid in
containment; power to pump is cut-off and restored with auto
maintenance selector switch.
VI.
Electrical
Control Panel
A.
All electrical
components shall be enclosed in a UL Listed, stainless steel
NEMA 4X control panel.
B.
Control system
shall be controlled by a fuel systems control card with the
following:
1.
Shall be mounted
and wired to quick disconnect devices.
2.
Shall utilize an
automotive grade microprocessor with built in memory.
3.
Card shall operate
from –40 Degrees to 180 Degrees F.
C.
Control panel
shall have the following:
1.
Will shut down all
arching devices on the over-fill or liquid in the
containment.
2.
Emergency shut-off
button.
3.
Alarm indicator
lights.
4.
Alarm reset.
5.
Automatic /
maintenance selector switch, key operated.
6.
Gauge for tank
level measured in percent.
7.
Panel light test.
VII.
Piping
A.
Shall be minimum
schedule 40 with forged steel fittings.
B.
Shall have flanged
connections where possible.
C.
Shall have
pressure relief to prevent pressure build-up from thermal
expansion.
VIII.
Assembly
A.
All assemblies
shall be with cadium-plated bolts, nuts, and lock washers.
B.
All units shall be
commercially sandblasted before painting.
C.
All paint shall be
fire resistant.
D.
All units shall be
completely assembled and operationally tested with approved
testing fluid prior to delivery.
E.
Tank, containment,
saddle, and ladder shall be UL 58-02-03 listed as a unit.
F.
Entire unit
assembled not to exceed 24,000 pounds empty.
Copyright Bryant Tank,
Inc. 1999