All Aviation / Bulkloading
Systems Shall Consist of the Following:
I.
Tank
II.
Containment Vessel
III.
Receiving System
IV. Delivery
System
V. Recirculation
System
VI. Fuel
Transfer
VII. Electrical
System
VIII. Power
Requirements
IX. Alarm
System
X. Control
Panel
XI. Piping
XII. Factory
Assembled
XIII. Operational
Manuals
XIV. Copyright
I.
Tank
A.
Shall be designed, constructed,
and labeled per UL 142 specifications.
B.
Shall be of single wall
construction, with all seams and fittings welded both inside
and outside of tank.
C.
Shall be horizontal and include
UL approved integrated support saddles for zone 4 seismic
conditions.
D.
Shall show date of
manufacturer’s test and manufacturer’s name.
E.
Shall be labeled for stationary
use only.
F.
Shall include lifting eyes (for
use when empty only) to lift entire unit.
G.
Shall have CAL/OSHA approved
ladder on tank.
H.
Interior shall be epoxy coated
for jet fuels.
I.
Shall have a manway with
inspection port.
J.
Shall have a low point drain
with a locking, non-freezing valve.
K.
Shall have permanent gauge stick
in tank.
L.
Shall have normal vent as
required.
M.
Shall have a UL required
emergency vent to meet or exceed NFPA-30 Firecode.
II.
Containment Vessel
A.
Shall be designed, constructed,
and labeled per UL142 specifications.
B.
Shall be of steel construction,
minimum 10 gauge.
C.
Shall be capable of containing
over 110% of the volume of the tank.
D.
Shall not exceed 12’ (twelve
feet) in width.
E.
Shall be skid mounted,
relocatable.
F.
Shall have a locking, low point
drain valve.
G.
Shall have lifting hooks on the
containment ends accessible from outside the containment
wall.
H.
Shall be leak tested with full
load of water after assembly.
III.
Receiving
System
A.
Shall have a drylock fill system
that prevents spillage of product during filling process.
B.
Shall be deadman controlled.
C.
Pump shall fuel at 200 gpm (two
hundred gallons per minute).
D.
Shall have stage 1 vapor
recovery.
E.
Shall be top filled with drop
tube within 6’’ of tank bottom.
F.
Shall have 200 gpm (two hundred
gallons per minute) aviation filter.
G.
Shall have slug valve to prevent
water contamination of fuel.
H.
All valves to be automatically
operated.
IV.
Delivery System
A.
Shall have a self-sealing
emergency valve threaded directly into the tank, with
breakaway provisions.
B.
Shall have a 212 degree F.
Fusible link that allows emergency valve to close in case of
fire.
C.
Shall have a meter with 200 gpm
(two hundred gallons per minute) capability.
D.
Shall have aviation filter.
E.
Shall have 5 micron filter
elements.
F.
Shall have coalescer element.
G.
Shall have slug valve to prevent
water contamination of fuel.
H.
Shall have deadman control.
I.
All valves to be automatically
operated.
J.
Emergency valve to be operated
outside of containment.
V.
Recirculation System
A.
Shall operate without deadman
control.
B.
Shall recirculate at 200 gpm
(two hundred gallons per minute).
C.
Shall filter all fuel through
aircraft type filter system.
D.
All valves to operate
automatically.
VI.
Fuel transfer shall include the following components:
A.
Shall have explosion proof
motor.
B.
Pump shall fuel at 200 gpm (two
hundred gallons per minute).
C.
Shall have air eliminator.
D.
Shall have aviation filter
separator with differential pressure gauge.
E.
Shall have four (4) filter
cartridges; one water coalescer, three (3) particulate.
F.
Shall have slug valve,
automatically controlled.
G.
Shall have sampling connections.
H.
Shall have low point float
assembly with positive water shut-off and manual low point
drain.
VII. Electrical System
A.
All electrical components shall
meet all applicable NEMA and UL Standards for class.
B.
All wiring shall conform to all
applicable NEC Standards for Class 1, Group D equipment.
C.
Area lighting shall be activated
by an on/off switch.
D.
Control circuits shall be 120
volt.
E.
Area and alarm lights shall be
explosion-proof
F.
Power requirements are 220/230
volt three-phase, 50 amp at load connection.
G.
Float switch in containment
shall be intrinsically safe.
H.
All operational modes (fill,
dispense, and recirculate) must be done from ground level
outside of containment.
VIII.
Power Requirements
A.
Pump motor shall be 230v
three-phase.
B.
Shall be explosion-proof.
C.
Deadman shall be intrinsically
safe.
IX.
Alarm System
A.
Shall be Class 1, Group D.
B.
Shall be both audible and
visual.
1.
Audible alarm shall incorporate
an alarm silence which will allow subsequent activation of
audible alarm.
2.
Visual alarm shall be a flashing
light that will not reset until alarm condition has been
cleared.
C.
System shall alarm at the
following conditions:
1.
High and low tank level alarm –
power to pump is cut off and restored with alarm silence.
2.
High and low cut off – power to
pump is cut off and restored with auto maintenance selector
switch.
3.
Liquid in containment – power to
pump is cut off and restored with auto maintenance selector
switch.
X.
Control Panel
A.
All
electrical components shall be controlled by a Bryant Fuel
System control panel installed inside a U.L. listed, NEMA –
4 box. This control panel is mounted on exterior containment
walls and operates in conformance with Class 1 Group D
areas.
1.
Control panel shall be mounted
and wired to quick disconnect devices.
2.
Control panel shall operate from
–40 degree Celsius to +180 degree Celsius.
B.
Control panel shall have the
following:
1.
Will shut down all arching
devices on overfill or liquid in containment alarm.
2.
Emergency shut-off button.
3.
Alarm indicator lights.
4.
Alarm reset.
5.
Automatic/maintenance selector
switch (key operated).
6.
Gauge for tank level (in
percent).
7. Panel light test.
XI.
Piping
A.
Shall have pressure relief to
prevent pressure build-up from thermal expansion.
B.
Shall be minimum schedule 40.
C.
Shall have flanged connections
where possible.
XII.
Factory Assembled
A.
All assembly shall be with
cadium plated bolts, nuts, and lock washers.
B.
All units shall be commercially
sandblasted before painting.
C.
All paint shall be fire
resistant.
D.
All units shall be completely
assembled, operationally and functionally tested with
approved testing fluid prior to delivery.
E.
Tank, containment, saddles, and
ladder shall be U.L. 58-02-03 listed as a unit.
F.
Entire unit assembled not to
exceed 25,000 pounds empty.
XIII.
Operational Manual
A.
Operational Manual is standard
with each unit.
B.
Certificate of operational tests
available prior to shipment.
C.
The complete fuel system shall
be self-contained with only the addition of electrical power
necessary to be a fully operational turnkey system.
XIV.
Copyright
A.
All units are copyrighted and
patented. Anyone attempting to duplicate the construction /
manufacture of the Bryant Fuel Cell without the express
written consent of Bryant Fuel Systems may be in violation
of Copyright or Patent laws.
B.
Copyright Bryant Tank, Inc.
1992.